Skip to content

How to size a furnace

Updated 2026-09-04 · 9 min read

Thermal-toned furnace and flue in a basement
Furnace and flue: the flue is warm because the exchanger is doing its job.

Four steps, and the third one is where nearly everyone stops early. Heating load, divide by AFUE, derate for altitude, then check the blower can carry the output inside the nameplate's temperature rise.

Start from the load

The heating load is the rate at which the house loses heat at the winter design temperature — the 99% design condition for your location, not the coldest night on record. In zone 5 that is around 45 BTU/h per square foot for an average envelope; the room-by-room worksheet gets closer than any per-foot number.

Heating loads are far larger than cooling loads in most of the country, because the design temperature difference is far larger: 72 degrees in Chicago against 19. That is why a house needs 100,000 BTU/h of heat and only three tons of cooling.

Output to input

A furnace nameplate carries both numbers. Input is fuel burned per hour; output is heat delivered to the air. AFUE is the seasonal ratio between them. Divide the load by AFUE to get the input you need to order:

input BTU/h = heating load ÷ AFUE

68,400 ÷ 0.96 = 71,250   →  an 80,000 BTU/h nominal furnace
68,400 ÷ 0.80 = 85,500   →  a 100,000 BTU/h nominal furnace

The same house needs a bigger box on a standard-efficiency furnace than on a condensing one, which is worth knowing before you compare two quotes with different nominal sizes.

The altitude derate

Above roughly 2,000 feet, thinner air means a gas appliance cannot burn its full rated input, and manufacturers derate about 4% per 1,000 feet. Denver costs a furnace about 13% of its nameplate. The furnace size calculator applies it automatically.

Thermal-toned house at altitude with a warm chimney
Thin cold air at altitude: the same furnace delivers less of what its plate promises.

High-altitude kits are a code requirement

Installing above the manufacturer's stated elevation without the correct orifice and pressure-switch kit produces incomplete combustion. The mechanical code makes the installation instructions binding, so this is not a judgement call.

The temperature-rise check

Every furnace has a rise range stamped on the plate — the allowed difference between return and supply air temperature. Airflow, rise and output are locked together: CFM = output ÷ (1.08 × rise). A furnace producing 76,800 BTU/h at a 55 °F rise needs about 1,290 CFM.

Airflow required by output and rise
Output40 °F55 °F70 °F
48,000 BTU/h1,110810635
64,000 BTU/h1,4801,080845
76,800 BTU/h1,7801,2901,015
96,000 BTU/h2,2201,6201,270

If the duct cannot deliver that airflow, the rise climbs past the top of the range, the limit switch trips and the furnace short-cycles. Measure static pressure before you decide the furnace is the problem.

Replacing an old furnace

The single worst method is matching the old nameplate. Furnaces installed before the 2000s were routinely oversized by half, and any house that has had new windows, air sealing or attic insulation since has a smaller load than it did. Calculate it fresh.

Thermal-toned furnace cabinet panel
The rating plate is the only place the two BTU/h numbers both appear.

One date to plan around: gas furnaces manufactured on or after 2028-12-18 must be at least 95% AFUE, against 80% today. That means condensing, which means PVC venting and a condensate drain. If your house currently vents into a masonry chimney, that venting work is coming — doing it once is cheaper than doing it twice.

Sources: 10 CFR 430.32(e)(1)(iii) (read 2026-09-04)

More in Heating 5 guides